INTRODUCTION
Hospital environment consists of high levels of potentially hazardous agents. Poor ventilation, excess temperature, chemicals, dust and microorganisms are the main indoor air problems in hospitals.[1] The microorganisms present in air rooms of the hospital may include pathogenic bacteria, virus, fungi, yeast and algae particles (bio-aerosol), which may be contributing factor for the overall health risk to the hospital personnel, patients and visitors.[2] Sources of bio-aerosols from hospital environments include cool mists, vaporisers, humidifiers, flush toilets and air conditioners. If the microorganisms have survived the aerial transport, they can grow and reproduce in the new environment and may spread further. About 1.5 million people become infected during their hospitalisations each year in the United State.[3] Contamination of hospital environment, particularly intensive care units (ICUs), operating theatres, etc., is considered among the most common life-threatening sources of nosocomial infections, especially to debilitated patients and patients undergoing surgical procedures requiring high level of environmental sterility (such as transplant surgery, open-heart surgery and cystoscopy).[4] Therefore, there is a need to monitor and prevent the generation, introduction and spread of air particles in hospital environments.[56]
Despite various limitations of measuring bio-aerosol concentration, recently some efforts have been put to investigate bio-aerosol pollutions in hospital environments.[78] Vonberg and Gastmeier,[9] Ruiz-Camps et al.,[10] and Armadans-Gil et al.[8] suggested that microbiological air sampling may be a useful method to detect increases in the concentrations of bio-aerosols in hospital environments. A direct relationship between bio-aerosols produced during hospital procedures and the respiratory system infections has been demonstrated.[11]
The choice of method for air sampling and analysis depends on many parameters such as environment type, agent type and count of microorganisms (less or more than 106 m−3). Microbiological content of the air can be usually detected by two methods.
Active detection
In which, the number of bio-aerosols present in the air is given in colony-forming units (CFUs)/m3 of air.[61213] The bio-aerosols in the air are detected by a microbiological air sampler that draws known volume of air physically through or over a particle collection device. This method is applicable when the amount of bio-aerosols is not very high.
Passive detection
In this method, the number of bio-aerosols present in air is given in CFU/plate/time (CFU/m2/h).[14] Standard Petri dishes containing culture media (settle plates) are exposed to the air for a given time to collect bio-aerosol particles; these 'sediment' are subsequently incubated. Passive detection has advantages such that the method is cheap, available everywhere and results obtained are reliable, reproducible and ate comparably valid results. Furthermore, many samples can be taken in different places at the same time.
The aim of bio-aerosol sampling is mainly to assess the contamination of a critical surface (wound, medicament and food) produced by the fallout of microorganisms coming from the air. Recently, for this purpose, the measurement of bio-aerosol air contamination by settling plates (passive sampling) appears in several official standards since it gives a direct indication of the microbial contamination of the surface. Both methods (passive and active sampling) are suitable for general monitoring of air contamination like routine surveillance programs. However, the choice must be made between one and the other to get specific information. If the air sampling performed during surgery is carried out to monitor the risk of microbial wound contamination, passive sampling is better than active sampling at predicting the likely contamination rate at the surgical room, as it allows a direct measure of the number of microorganisms settling on surfaces. On the other hand, if the sampling is performed to obtain information on the concentration of all inhalable viable particles, the active method should be done.[15]
According to previous researches, both the amount and type of microorganisms that exist in the hospital environment are important and related to nosocomial activities.[16] Therefore, we decided in this study to identify the types and estimate the amount of contamination particles (bacteria and fungi) by passive method in various units of five hospitals in Kermanshah city, Iran. The hospitals involved in the study were Imam Ali Hospital (IAH), Taleghani Hospital (TH), Imam Khomeini Hospital (IKH), Farabi Hospital (FH) and Imam Reza Hospital (IRH). Culture-able airborne bio-aerosols were recovered and quantified using six-stage Andersen samplers.
To the best of our knowledge, there is no report that determines the type and level of contamination in various units of these hospitals in Kermanshah, Iran.
MATERIALS AND METHODS
The sampling site
The study was performed in five hospitals in Kermanshah, Iran, between December 2016 and February 2017. Air samples were collected from several units in each hospital, including the surgery, ICU, angiography, emergency, oncology, nurses station, pathology laboratory, microbiological laboratory, operating room, isolation room (infectious section), delivery room and outdoors. Each area in the hospital was visited three times. Air sampling with 283 L value was performed at a height of 1.5 m above ground level during 10 min to simulate the breathing zone.
Statistical analysis
Results were expressed as mean values and percentages. The limit of statistical significance was P = 0.05. All data analyses were performed using the Statistical Packages for the Social Sciences (SPSS) version 22 (IBM, Chicago, IL, USA). Furthermore, all the experiments were determined in triplicate and repeated three times to ensure reproducibility.
RESULTS AND DISCUSSION
The aim of bio-aerosol sampling is mainly to assess the contamination of a critical surface (wound, medicament and food) produced by the fallout of microorganisms coming from the air. Recently, for this purpose, the measurement of bio-aerosol air contamination by settling plates (passive sampling) appears in several official standards since it gives a direct indication of the microbial contamination of the surface. Both methods (passive and active sampling) are suitable for general monitoring of air contamination like routine surveillance programs. However, the choice must be made between one and the other to get specific information. Especially, if the air sampling performed during surgery is carried out to monitor the risk of microbial wound contamination, passive sampling is better than active sampling at predicting the likely contamination rate at the surgical room, as it allows a direct measure of the number of microorganism settling on surfaces. On the other hand, if the sampling is performed to obtain information on the concentration of all inhalable viable particles, the active method should be done.[15] The current study investigated air contamination in the environment of five hospitals in Iran by passive method. The World Health Organization (WHO) has suggested relatively relaxed limits of 100 CFU/m3 for bacteria and 50 CFU/m3 for fungi in the air of hospitals.[17] Therefore, quantitative and qualitative outcomes of this study demonstrate that contamination level and microbial variety in the studied hospitals are not farfetched from the WHO standards, especially with regard to fungal counts.
A few similar studies have been carried out in other hospitals in Iran. Eslami et al.[18] found that the most prevalent bacteria identified were Staphylococcus epidermidis (75%) in the air of eye operating room and Staphylococcus saprophyticus (52%) in the internal ICU and isolation room. The most prevalent fungi identified in the air of selected wards were related to Alternaria alternata (43%), Aspergillus flavus (24%), Penicillium (36%) and Curvularia (21%). Mirzaei et al.[19] collected 72 samples from three emergency rooms and three operating rooms that 17 types of bacteria were detected, including Staphylococcus, Micrococcus, Viridans streptococci Pneumococcus, Escherichia coli, Streptococcus, Bacillus cereus, Bacillus subtilis, Klebsiella, Pseudomonas, Diphtheroid, Citrobacter and Enterobacter. The most prevalent bacteria in this study were Actinomycetes spp. (75.34%, from the outdoor air of IAH) and S. epidermidis (47.72%, from the air of nurses station of IKH). While the predominant fungal air contaminant was yeast (79%, from the outdoor air of IAH) and Candida spp. (56.12%, from the surgery room of IRH), Gizaw et al.[20] reported that Staphylococcus aureus and Streptococcus pyogenes were found in most of the hospital wards.
Imam Ali and Taleghani Hospitals
Table 1 presents the average bio-aerosol contaminant (bacteria and fungi) levels in the surgery units and the outdoor environments of IAH and TH during open-heart surgery and 3 h after open-heart surgery.
Table 1: The average level of bio-aerosols (bacteria and fungi, colony-forming units/m3) in different rooms of Imam Ali and Taleghani Hospitals
The Gram-positive bacteria (Bacillus spp. and Actinomycete spp.) and fungi (yeast) in outdoor air of IAH were 11 (<100) and 11 CFU/m3, respectively. Airborne bacteria and fungus particles were not detected from the surgery room environment of IAH. The absence of airborne bio-aerosols in the surgery room air compared to outdoor air indicated the presence of a sufficiently controlled system in IAH. The healthcare workers' (HCWs) standard limit is <100 and <50 CFU/m3 for bacteria and fungi, respectively, in hospital rooms. According to HCWs' standard, IAH has the recommended environmental air condition.
S. aureus, 7 CFU/m3, and fungi (yeast), 14 CFU/m3, were isolated from ICU of IAH. Furthermore, S. epidermidis and Bacillus spp. (Gram-positive bacteria) were isolated from the air of the angiography room with count of 7 and 11 CFU/m3, respectively, but no any fungus particles isolated from this room at IAH. According to the combined results above, the indoor environment of IAH compared to the outdoor environment is safer.
In TH, air sampling of the old surgery room was done 3 h after an open-heart surgery. The bacteria and fungus particles were not detected in the air of old surgery and old ICU rooms. In the new surgery room, 250 CFU/m3 of S. epidermidis which is regarded as unsafe according to HCWs' standard. However, no fungus particles were isolated from this room. In the outdoor air, the major contaminant was S. epidermidis (>100 CFU/m3) and yeast (43 CFU/m3).
At the emergency unit of TH various types of bacteria, Corynebacterium spp. (>100 CFU/m3), S. aureus (11 CFU/m3), Actinomycetes spp. (7 CFU/m3) and fungi ([yeast] 7 CFU/m3) were isolated. Therefore, this environment has not met the HCWs' standard for the hospital personnel and the patients. According to the above results, the indoor environment of TH compared to the outdoor environment is more polluted.
According to the above results of IAH and TH, the environment of IAH (25 CFU/m3 total contamination of bacteria and 14 CFU/m3 total contamination of fungi) compared to TH (558 CFU/m3 total contamination of bacteria and 11 CFU/m3 total contamination of fungi) is very safe.[21]
Airborne indoor bacteria could be related to frequent movements of many individuals (patients, attendants, visitors and healthcare personnel).[22] Furthermore, airborne indoor fungi come from two sources: (1) the outdoor air and (2) the indoor fungal colonisation (colonisation originates mainly in every wet, dark and poorly ventilated area).[23]
All the isolated bacteria and fungi in IAH and TH are Gram positive and yeast, respectively, similar to what was observed in other hospital's bio-aerosol studies. In our study, the total count for IAH was 25 CFU/m3 for bacteria and 14 CFU/m3 for fungi. This was slightly lower than levels reported from hospitals in Spain,[24] Sweden,[15] Palestine,[4] the United Arab Emirates[25] and India.[26] However, TH environment has higher levels of Gram-positive bacteria compared to some the above-mentioned hospitals.
Imam Khomeini and Farabi Hospitals
Table 2 presents the average level of bio-aerosol contaminants (bacterial and fungi) in some selected hospital rooms and outdoor environments of IKH and FH.
Table 2: The average level of bio-aerosol contaminants (bacteria and fungi, colony-forming units/m3) in different rooms of Imam Khomeini and Farabi Hospitals
There were no bacteria and fungus particles detected in outdoor air of IKH. All rooms and laboratories of IKH were contaminated with high level (>100 CFU/m3) of various Gram-positive bacteria such as S. epidermidis, S. aureus and S. saprophyticus. However, the total count of fungi was low (46 CFU/m3 and 10 CFU/m3) for yeast and Aspergillus spp., respectively. The above results indicated that the quality of the air at hospital rooms of IKH was poor according to HCWs' standard.
The various types of Gram-positive bacteria (S. epidermidis, S. aureus, Bacillus spp. and Actinomycete spp.) and fungi (Candida spp., Penicillium spp. and yeast) were isolated from the outdoor air of FH. The average amount of Gram-positive bacteria and fungi in the ICU and the laboratory is very low compared to the average outdoor levels. According to our findings, the air at the environment of FH (47 CFU/m3 total contamination of bacteria and 7 CFU/m3 total contamination of fungi) appeared cleaner compared to that of IKH (3189 CFU/m3 total contamination of bacteria and 84 CFU/m3 total contamination of fungi). However, the isolated yeast fungi of IKH and FH have not potential opportunistic microorganisms for nosocomial infections.[192021]
Some authors reported that the airborne bacteria and fungi in hospital at Poland were 257–436 and 10–96 CF', respectively.[27] Other studies have reported similar findings from various countries including Taiwan (1–423 and 0–319 CFU/m3),[28] Canada (14–131 and 50–611 CFU/m3),[29] Spain (6.6–73.5 and 0.03–46.01 CFU/m3),[24] Italy (42–374 and 0–28 CFU/m3)[30] and India (10–150 and 45–120 CFU/m3)[26] for bacteria and fungi, respectively. The high level of bio-aerosol contaminant recorded at IKH might be considered as possible reservoirs for opportunistic nosocomial infections in that hospital.
Imam Reza Hospital
The average level of bio-aerosol contaminants (bacterial and fungi) in various units of IRH is shown in Table 3.
Table 3: The average level of bio-aerosol contamination (bacteria and fungi, colony-forming units/m3) in different rooms of Imam Reza Hospital
There were no bacteria or fungus particles detected in the outdoor air, the operation and the delivery rooms of IRH. However, we isolated Lactobacillus spp. (14 CFU/m3), S. aureus (25 CFU/m3), S. epidermidis (11 CFU/m3), Bacillus spp. (21 CFU/m3), Listeria spp. (14 CFU/m3), E. coli (7 CFU/m3) and Mucor (4 CFU/m3) in the surgery room, ICU, emergency room, angiography room, isolated room (infectious section), pathology laboratory and the microbiological laboratory of IRH, respectively. Various types of fungi (yeast: 64 CFU/m3, Candida albicans: 18 CFU/m3 and A. flavus: 4 CFU/m3) were detected. According to above results and HCWs' standard, IRH has a safe condition from the point of bacterial level and pollute from the point of the fungal level.
Our results were considerably lower than those previously reported by Curtis et al.,[31] by Doleźal et al.,[32] by Kelsen and McGuckin,[33] by Kotlarek-Haus et al.[34] and by Nunes et al.[35]
Based on the results, the following recommendations may be considered to mitigate bio-aerosol generation and transmission:
- For hospital designers: Designing a better ventilation system or adding bed head removable return air inlets, which can be employed during nebulization therapy or when patients are coughing
- For managers and nurses: Using screens or individual rooms for separate patients
- For cleaners: Using low volatile organic compound emission detergents
- For nurses: Making bed gently and strictly using personal protective clothing (mask) during nebulization therapy or when patients are coughing.
CONCLUSIONS
In this study, bio-aerosol particle (bacteria and fungi) contamination in some hospitals of Iran (IAH, TH, IKH, FH and IRH) was investigated. Significant level of air contamination by bacteria (>100 CFU/m3) was detected at IAH, TH and IKH, and significant fungus particles (>100 CFU/m3) were detected at IRH. Very low level of bio-aerosol contamination was detected at FH. However, a low number of air microorganisms do not mean a clean and healthy environment. Therefore, comprehensive studies are necessary to determine health risk associated with the air environment of these hospitals.
Financial support and sponsorship
Kermanshah University of Medical Sciences, for supporting this study financially from the Grant No. 96515.
Conflicts of interest
There are no conflicts of interest.
Acknowledgements
We gratefully acknowledge Vice-Chancellor for Research and Technology, Kermanshah University of Medical Sciences, for financial support of this study resulting from MSc Microbiology thesis of Mahsa Dastranj, Kermanshah University of Medical Sciences, Iran (Grant No. 96515).
REFERENCES
1. Husman T. Health effects of indoor-air microorganisms Scand J Work Environ Health. 1996;22:5–13
2. Cornejo-Juárez P, Vilar-Compte D, Pérez-Jiménez C, Ñamendys-Silva SA, Sandoval-Hernández S, Volkow-Fernández P, et al The impact of hospital-acquired infections with multidrug-resistant bacteria in an oncology Intensive Care Unit Int J Infect Dis. 2015;31:31–4
3. Rhame FSBennett JV, Brachman PS. The inanimate environment Hospital Infections. 1998 Philadelphia Lippincott-Raven Publishers:299–324
4. Al Laham NA. Prevalence of bacterial contamination in general operating theaters in selected hospitals in the Gaza Strip, Palestine J Infect Public Health. 2012;5:43–51
5. Mangram AJ, Horan TC, Pearson ML, Silver LC, Jarvis WR. Guideline for prevention of surgical site infection, 1999. Hospital infection control practices advisory committee Infect Control Hosp Epidemiol. 1999;20:250–78
6. Center for Disease Control and Prevention. Guidelines for Environmental Infection Control in Health-Care Facilities. 2003 Atlanta, GA CDC
7. He C, Mackay IM, Ramsay K, Liang Z, Kidd T, Knibbs LD, et al Particle and bioaerosol characteristics in a paediatric Intensive Care Unit Environ Int. 2017;107:89–99
8. Armadans-Gil L, Rodríguez-Garrido V, Campins-Martí M, Gil-Cuesta J, Vaqué-Rafart J. Particle counting and microbiological air sampling: Results of the simultaneous use of both procedures in different types of hospital rooms Enferm Infecc Microbiol Clin. 2013;31:217–21
9. Vonberg RP, Gastmeier P. Nosocomial aspergillosis in outbreak settings J Hosp Infect. 2006;63:246–54
10. Ruiz-Camps I, Aguado JM, Almirante B, Bouza E, Ferrer Barbera C, Len O. Guidelines for the Treatment of Invasive Fungal Disease by Aspergillus spp. and Other Fungi Issued by the Spanish Society of Infectious Diseases and Clinical Microbiology (SEIMC). 2011 Update Enferm Infecc Microbiol Clin. 2010;28:172.e1–21
11. Harrel SK, Molinari J. Aerosols and splatter in dentistry: A brief review of the literature and infection control implications J Am Dent Assoc. 2004;135:429–37
12. Blomquist G. Sampling of biological particles Analyst. 1994;119:53–6
13. Pasquarella C, Albertini R, Dall'aglio P, Saccani E, Sansebastiano GE, Signorelli C, et al Air microbial sampling: The state of the art Ig Sanita Pubbl. 2008;64:79–120
14. Friberg B, Friberg S, Burman LG. Inconsistent correlation between aerobic bacterial surface and air counts in operating rooms with ultra clean laminar air flows: Proposal of a new bacteriological standard for surface contamination J Hosp Infect. 1999;42:287–93
15. Napoli C, Marcotrigiano V, Montagna MT. Air sampling procedures to evaluate microbial contamination: A comparison between active and passive methods in operating theatres BMC Public Health. 2012;12:594
16. Schaal KP. Medical and microbiological problems arising from airborne infection in hospitals J Hosp Infect. 1991;18(Suppl A):451–9
17. Kowalski W. UVGI for hospital applications Int Ultraviolet Assoc News. 2008;10:30–4
18. Eslami A, Karimi F, Karimi Z, Rajabi Z. A survey of the quantity and type of biological aerosols in selected wards of a teaching hospital in Ghazvin Electron Physician. 2016;8:2281–5
19. Mirzaei R, Shahriary E, Qureshi MI, Rakhshkhorshid A, Khammary A, Mohammadi M. Quantitative and qualitative evaluation of bio-aerosols in surgery rooms and emergency department of an educational hospital Jundishapur J Microbiol. 2014;7:e11688
20. Gizaw Z, Gebrehiwot M, Yenew C. High bacterial load of indoor air in hospital wards: The case of University of Gondar teaching hospital, Northwest Ethiopia Multidiscip Respir Med. 2016;11:24
21. Groll AH, Walsh TJ. Uncommon opportunistic fungi: New nosocomial threats Clin Microbiol Infect. 2001;7(Suppl 2):8–24
22. Memon BA, Bhutto GH, Rizvi WH. Measurement of air contamination in different wards of public sector hospital, Sukkur Pak J Pharm Sci. 2016;29:2015–21
23. Al-Doory Y. The indoor airborne fungi N Engl Reg Allergy Proc. 1985;6:140–9
24. Ortiz G, Yagüe G, Segovia M, Catalán V. A study of air microbe levels in different areas of a hospital Curr Microbiol. 2009;59:53–8
25. Uduman SA, Farrukh AS, Nath KN, Zuhair MY, Ifrah A, Khawla AD, et al An outbreak of
Serratia marcescens infection in a special-care baby unit of a community hospital in United Arab Emirates: The importance of the air conditioner duct as a nosocomial reservoir J Hosp Infect. 2002;52:175–80
26. Sudharsanam S, Swaminathan S, Ramalingam A, Thangavel G, Annamalai R, Steinberg R, et al Characterization of indoor bioaerosols from a hospital ward in a tropical setting Afr Health Sci. 2012;12:217–25
27. Augustowska M, Dutkiewicz J. Variability of airborne microflora in a hospital ward within a period of one year Ann Agric Environ Med. 2006;13:99–106
28. Li CS, Hou PA. Bioaerosol characteristics in hospital clean rooms Sci Total Environ. 2003;305:169–76
29. Marc YG, Duchaine VC. Airborne bacteria and antibiotic resistance genes in hospital rooms Aerobiologia. 2010;26:185–94
30. Pasquarella C, Vitali P, Saccani E, Manotti P, Boccuni C, Ugolotti M, et al Microbial air monitoring in operating theatres: Experience at the university hospital of Parma J Hosp Infect. 2012;81:50–7
31. Curtis L, Cali S, Conroy L, Baker K, Ou CH, Hershow R, et al Aspergillus surveillance project at a large tertiary-care hospital J Hosp Infect. 2005;59:188–96
32. Doleźal M, Doleźal M, Pawliszyn W, Sliwa A, Owsiński J, Hartwich A, et al Atmospheric microflora in hospital wards and everyday hospital routine Pol Tyg Lek. 1978;33:613–6
33. Kelsen SG, McGuckin M. The role of airborne bacteria in the contamination of fine particle neubilizers and the development of nosocomial pneumonia Ann N Y Acad Sci. 1980;353:218–29
34. Kotlarek-Haus S, Nowicka I, Juzwiakowa J, Siemek R. Analysis of bacterial pollution of the air in wards of haematological department Pol Tyg Lek. 1980;35:1149–52
35. Nunes ZG, Martins AS, Altoe AL, Nishikawa MM, Leite MO, Aguiar PF, et al Indoor air microbiological evaluation of offices, hospitals, industries, and shopping centers Mem Inst Oswaldo Cruz. 2005;100:351–7