Indoor Particles and Symptoms Among Office Workers: Results from a Double-Blind Cross-Over Study

Mendell, Mark J.1; Fisk, William J.2; Petersen, Marty R.1; Hines, Cynthia J.1; Dong, Maxia2; Faulkner, David2; Deddens, James A.1; Ruder, Avima M.1; Sullivan, Douglas2; Boeniger, Mark F.1

Free Access
Article Outline
Collapse Box

Author Information

From 1National Institute for Occupational Safety and Health, Cincinnati, OH; and

2Lawrence Berkeley National Laboratory, Berkeley, CA.

Address correspondence to: Mark J. Mendell, Lawrence Berkeley National Laboratory, 1 Cyclotron Road, MS 90-3058, Berkeley, CA 94720; mjmendell@lbl.gov

This work was supported by NIOSH/CDC; by the Assistant Secretary for Energy Efficiency and Renewable Energy, Office of Building Technology, State and Community Programs of the U.S. Department of Energy (DOE) under Contract No. DE-AC03-76SF00098; and by the Office of Research and Development, U.S. Environmental Protection Agency (EPA). Opinions expressed in this paper do not imply official endorsement by DOE or EPA.

Submitted 2 March 2001; final version accepted 18 January 2002.

Collapse Box

Abstract

Background. We studied the effects of removing small airborne particles in an office building without unusual contaminant sources or occupant complaints.

Methods. We conducted a double-blind crossover study of enhanced particle filtration in an office building in the Midwest United States in 1993. We replaced standard particle filters, in separate ventilation systems on two floors, with highly efficient filters on alternate floors weekly over 4 weeks. Repeated-measures models were used to analyze data from weekly worker questionnaires and multiple environmental measurements.

Results. Bioaerosol concentrations were low. Enhanced filtration reduced concentrations of the smallest airborne particles by 94%. This reduction was not associated with reduced symptoms among the 396 respondents, but three performance-related mental states improved; for example, the confusion scale decreased (−3.7%; 95% confidence limits (CL) = −6.5, −0.9). Most environmental dissatisfaction variables also improved;eg, “stuffy” air, −5.3% (95% CL = −10.3, −0.4). Cooler temperatures within the recommended comfort range were associated with remarkably large improvement in most outcomes; for example, chest tightness decreased −23.4% (95% CL = −38.1, −8.7) for every 1°C decrease.

Conclusions. Benefits of enhanced filtration require assessment in buildings with higher particulate contaminant levels in studies controlling for temperature effects. Benefits from lower indoor temperatures need confirmation.

Indoor work environments such as offices have traditionally been considered free of harmful exposures. In the last 2 decades, however, indoor workers have complained increasingly of acute symptoms and discomfort. Reported symptoms have included eye, nose, and throat irritation, headache and fatigue, dry or irritated skin, and breathing problems. This group of complaints, sometimes called sick building syndrome symptoms, will be referred to here as building-related symptoms.

Available scientific evidence suggests that building-related symptoms are associated with a combination of chemical, microbiological, physical, and psychosocial exposures, and that current exposure assessment strategies do not adequately characterize some of these. 1 A number of studies have now documented objectively measurable health effects to be associated with subjectively reported building-related symptoms or with changes in indoor environments. 2–4

Identified risk factors for building-related symptoms include air conditioning or humidification systems, carpets, lower outdoor air ventilation rates, higher levels of Gram-negative bacterial endotoxin, higher temperatures, and very low relative humidities. 1,5,6 Evidence suggests that increased levels of some indoor contaminants increase occupant symptoms and environmental dissatisfaction. 7,8 Other evidence suggests that thermal conditions, possibly in conjunction with indoor pollutants, influence perceived air quality. 9–11

Most field studies in this area have been cross-sectional and observational. 1 These have identified risk factors and generated hypotheses but have associated few measured exposures with building-related symptoms. Experimental studies, 1,2,12,13 by changing one factor at a time, can better isolate direct effects.

This study was suggested by observations that particulate contaminants or their sources are associated with acute occupant symptoms in indoor office and residential environments 6,7,14–17 and that irritant contaminants may increase sensations of stuffy, dry air. 7,18 The goal of this study was to assess benefits of a generalizable intervention, rather than a building-specific mitigation.

Back to Top | Article Outline

Methods

Study methods, described elsewhere, 19 are briefly summarized here. A double-blind, multiple crossover intervention design was used in summer 1996 to assess benefits for symptoms and comfort of the enhanced removal of small airborne indoor particles through improved central filtration. The study protocol was granted exemption by the Institutional Review Board of the National Institute for Occupational Safety and Health. The experimental study spaces were two separate floors (floors 2 and 4, with 185 and 307 workers) of mostly “open plan” partitioned office space within a large office building (1900 m2). The building, located in the midwestern United States, was occupied by office workers from a government agency. Building management had reported sporadic occupant complaints about comfort, but not about symptoms. Smoking was not permitted within the building.

Back to Top | Article Outline
Intervention Methods

The study was performed in a hot-summer region so ventilation systems would supply minimum outdoor air throughout the study. Stable, low outdoor air ventilation rates were considered optimal conditions for studying the benefits of enhanced filtration.

The study began with installation of clean conventional filters in the ventilation systems of both study floors. Filter location was in the air stream of mixed outside and recirculated air. After 2 weeks of baseline measurements, highly efficient particle filters were installed in the ventilation system of floor 4 during the weekend and left installed for 1 week. The next weekend, conventional filters were reinstalled on floor 4 and the enhanced filters installed in the ventilation system of floor 2. This pattern was repeated in intervention weeks 3 and 4.

The estimated efficiency of the normal filters was 3%, 15%, 40%, and 80% for particles with diameters of 0.3, 0.85, 1.5, and 3 μm. 20 The high efficiency filters had an efficiency rating of 95% at 0.3 μm with higher efficiencies for both smaller and larger particles. 21 Building occupants and staff were blind to both the schedule and type of intervention (except contract staff maintaining the ventilation system, who agreed not to disclose this information).

Back to Top | Article Outline
Questionnaire Methods

An initial self-completed background questionnaire for workers collected informed consent, demographic data, and information on location, health history, job, and job stressors. Shorter weekly questionnaires assessed a variety of outcomes, including:

* Severity that day of eight symptoms (seven previously associated with indoor air quality and one set of “control” symptoms assumed unrelated to indoor air quality – sore back, shoulders, or neck).

* Performance-related mental states, hypothesized to be related to indoor air quality. Two of these, mental confusion and fatigue, were assessed by five-question mood sub-scales from the Neurobehavioral Evaluation System, 22 a set of computerized neurobehavioral tests, administered here with paper and pencil. The third used a single question about self-assessed productivity.

* Aspects of environmental dissatisfaction, including three hypothesized to be potentially affected by particulate contamination (stuffy, dusty, too dry)

* Perceived environmental changes, to assess blinding of the intervention.

The use of a visual analog scale (VAS) for symptoms follows Wyon, 2 although symptoms were assessed here using rows of 26 circles to allow electronic scanning of responses. Pretesting found similar within-person variability from this format and traditional VAS lines. 23 Questions on productivity-related mental states and on environmental dissatisfaction provided five response categories: “not at all,” “a little,” “moderately,” “quite a bit,” and “extremely.” Workers received questionnaires each Thursday morning, with instructions to complete them in the afternoon on Thursday or Friday. Each study week, all workers present Thursday or Friday were eligible. Study staff blinded to the intervention schedule handled questionnaires and interactions with workers.

Back to Top | Article Outline
Environmental Measurements

Environmental measurements included temperature, humidity, carbon dioxide concentration, and effective outdoor air ventilation rate, all unaffected by the intervention and potentially requiring adjustment in analyses. Airborne contaminants potentially affected by the intervention, and therefore not adjusted in analyses, were also measured: concentrations of particles, endotoxin, ergosterol, and beta-1,3-glucans. Air temperature and humidity were measured and logged continuously at multiple locations on each floor. The humidity metric used was the humidity ratio (the mass of water vapor divided by the mass of dry air), which is independent of temperature. For both humidity and temperature, analyses used the time-weighted values in the space where each respondent worked, during the workday on which the questionnaire was completed. Details on environmental measurements are provided elsewhere. 19,24–26

Back to Top | Article Outline
Data Analysis

Intervention effectiveness was assessed with models containing terms for week, location, person, and intervention. We assumed that the levels of the response variables were equally spaced. Modeling was performed in SAS, version 6.12, 27 using for each of 18 outcomes a mixed linear model (PROC MIXED) with a random person effect, maximum likelihood estimation, and assumption of a compound symmetric covariance structure. These models produced unadjusted estimates and, after potential inclusion of other covariates (temperature, humidity ratio, carbon dioxide, ventilation rate, and job stress), adjusted estimates. Analyses assumed a same-week filtration effect with no residual effect during the following week. Estimated standard errors were used to calculate 95% confidence limits (CLs) (or confidence intervals [CIs]), without adjustment for calculation of multiple estimates. Adjusted effect estimates were calculated for each outcome as the absolute change and as the percentage of the mean, with 95% CLs (or CIs).

Back to Top | Article Outline

Results

Of 457 initially eligible respondents among 492 workers on the two floors, 396 (135 on floor 2, 261 on floor 4) returned the background questionnaire and consent form, for an 81% initial response rate. During the 4 crossover weeks, response rates were substantially lower, averaging 63%, with usable questionnaires averaging 58%.

Table 1 shows demographic characteristics among initial respondents. Differences between the respondents on the two floors were greatest for job, education, and military status; however, within-person data analyses made these differences unlikely to affect the findings. Those who completed at least two questionnaires during the intervention (Table 1) differed demographically only slightly from the entire group completing the initial questionnaire. As the latter included 81% of eligible workers on the study floors, participants in the intervention were reasonably representative of all eligible workers. Responses to questions designed to assess blinding of the intervention showed that participants were not aware of the specific times or nature of the enhanced filtration intervention. Almost all perceived changes reported relative to the previous week concerned temperature.

Table 1
Table 1
Image Tools

Initial symptom prevalences were close to average for U.S. office buildings;eg, initial prevalence of weekly work-related eye irritation was 20% in this population compared with 17% in representative U.S. office buildings surveyed by the U.S. EPA (fax communication, Howard L. Brightman, October 1998). Weekly average carbon dioxide concentrations in the study spaces (range 589–738 parts per million) were typical for U.S. office buildings. 19 Ventilation rates were typical as well (range 9.0–16.2 liters per second per person, estimated using the effective outside air ventilation rates for Thursday and Friday of each week, and average occupancies of 165 and 280 for floors 2 and 4, respectively). For each floor, outdoor air ventilation rate was nearly constant throughout the study (Table 2), providing outdoor air at the minimum settings. Airflow measurements confirmed that, consistent with engineering predictions, the enhanced filtration produced no measurable reduction of ventilation airflow.

Table 2
Table 2
Image Tools

Table 2 summarizes weekly environmental parameters by floor. Indoor temperatures (22.2–25.6°C) and relative humidities (42–58%) were mostly within the accepted summer comfort limits of 22.8–26.1°C at 50% relative humidity. 28 Indoor air concentrations of the fungal indicators measured were mostly below detection limits;ie, for seven of eight ergosterol samples (the detectable value, 2.6 × 10−4 ng/m3, was about 40% of the outdoor levels) and for 17 of 30 beta-1,3-glucan samples (the maximum indoor air concentration, 1.2 ng/m3, was less than one third of the median outdoor concentration). As previously reported, 24 air levels of endotoxin (an indicator of Gram-negative bacteria) were very low, with 23% of samples below the detection limit and a geometric mean of 0.24 endotoxin units/m3.

Enhanced filtration reduced airborne concentrations of 0.3–0.5 micron particles, the smallest we measured, by 94% (Table 2). Size-specific particle number concentrations were reduced by 84% for 0.5–0.7 μm, 72% for 0.7–1.0 μm, 55% for 1.0–2.0 μm, and 16% for >2.0 μm particles. 21 Benefits of high efficiency filtration over conventional filtration decreased as particle size increased (Table 2), presumably because of increasing efficiency of conventional filters with larger particles. Furthermore, there was no evidence that enhanced filtration reduced the already low air concentrations of endotoxin, as reported elsewhere. 24

On each floor, the highest values for both symptom severities and environmental discomfort occurred during week 1, and most decreased substantially afterward, even before the filtration intervention began in week 3 (data not shown).

Each outcome model contained identical covariates. Because ventilation during the study was nearly stable, related metrics (carbon dioxide concentrations and effective ventilation rates) were only weakly correlated with occupant outcomes and were not included in models. Two thermal parameters, indoor temperature and indoor humidity ratio, were strongly correlated with most outcomes and were included in all models.

Table 3 provides both unadjusted and multivariate-adjusted estimates from the models of changes in occupant outcomes associated with the intervention. As all reported outcomes are adverse, negative estimated changes represent improvements. Adjusted estimates were generally similar in magnitude to unadjusted, except that with adjustment fewer symptom outcomes showed improvement with enhanced filtration. Table 3 also shows multivariate-adjusted changes in outcomes associated with decreasing temperature.

Table 3
Table 3
Image Tools

Figure 1 shows adjusted estimates and 95% CIs for change in outcomes, as percent of outcome means, associated with enhanced filtration and per 1°C decrease in temperature. With enhanced filtration, no symptom showed strong evidence of change; all CIs were broad. Skin symptoms showed a potential worsening, with eye and throat symptoms showing lesser potential worsening. With enhanced filtration, 95% CIs for 5 of 17 outcomes (excluding the control outcome) excluded or nearly excluded the null, all with estimated improvements. Performance-related mental states all showed improvement (and relatively narrow CIs, which can be calculated from Table 3)—mental confusion scale, −3.7%; fatigue scale, −2.5%; and “less productive,” −2.1%. The environmental dissatisfaction variables that most clearly improved with enhanced filtration were “too humid,” −7.0%; “stuffy,” −5.3%; and, to a lesser extent, both “too cold,” −5.5% and “too warm,” −3.5%.

Figure 1
Figure 1
Image Tools

Lower temperatures, even within the accepted summer comfort range, were strongly related to improvements in all adverse outcomes, including the control outcome, except two: “too cold” and “drafty” (Figure 1). For the 16 outcomes showing improvement, all 95% CIs excluded 0%. Each 1°C decrease in temperature was related to a 19% decrease in severity of eye symptoms and to decreases in “stuffy” and “too warm” (19% and 25%) that greatly exceeded the related increases in “drafty” or “too cold” (2% and 3%).

Within the observed 42–50% range of relative humidity, an increase of 1 × 10−3 humidity ratio units (roughly equivalent to increased relative humidity of 6.7% within the observed range), was associated with at least small improvements in all outcomes except “too dry” and “too humid”; however, 95% CIs excluded 0% only for chest (−38.4%, 95% CL = −60.6, −16.3), throat (−19.1%, 95% CL = −37.4, −0.7), and fatigue symptoms (−14.7%, 95% CL = −27.5, −1.8). These were roughly comparable to the estimated benefits of decreasing temperature by 1.6, 1.4, and 0.9°C, respectively, at constant humidity (data not shown).

Back to Top | Article Outline

Discussion

In this office building without known unusual sources of contamination or evident health complaints from occupants, enhanced removal of small particles from the indoor air was not associated with reduced symptoms. Still, the 94% reduction achieved here in 0.3–0.5 micron airborne particles and lesser reductions in larger particles were associated with small improvements in all performance-related mental states assessed and most measures of environmental dissatisfaction (including the improvement predicted for “stuffiness”). Chance, although perhaps explaining small improvements in many of these outcomes, does not provide a plausible explanation for the reductions observed in mental confusion, perceived environmental stuffiness, and perceived excess humidity (−4%, −5%, and −7%, respectively). These strong associations would not have been expected by chance among 18 outcomes, if there were no true relationship. The −2.5% improvement on the five-item fatigue scale suggests a small reduction in fatigue, despite the +0.6% worsening on the single-item fatigue symptom question.

Back to Top | Article Outline
Assessment of Study Validity

Design strategies used in this study should have increased validity relative to some other indoor environmental studies. The double-crossover intervention design used repeated measures and within-subject analyses to compare study groups with the same employer, within the same building, and with separate but identical ventilation systems. This design reduced potential bias from differences in stable environmental, job, and personal factors between the two groups. Within-person analyses adjusted for weekly individual levels of work stress reduced potential bias from high (and changing) levels of worker stress related to impending layoffs. The double-blind condition, successfully maintained, prevented bias from suggestion effects among both participants and study staff. Three elements of the study protected against bias from the previously observed weekly decrease in symptoms on repeated symptom questionnaires 12,29,30: delaying the crossover intervention until the 3rd study week when outcome reporting was more stable, using a simultaneous comparison group without the intervention, and adjusting for week of study in analyses. The study assessed current outcomes to reduce recall bias, measured and analyzed these as continuous outcomes to increase sensitivity relative to matched analyses of dichotomous outcomes, and compared outcome data from the same time period as the environmental measurements.

We measured temperature, humidity, and ventilation rate to allow adjustment in analysis, as these cannot be precisely controlled in field studies and have been previously associated with symptoms and discomfort in occupants. 1,31 Residual confounding by temperature could not have produced the benefits found here from enhanced filtration, as average temperatures for the two filtration conditions were essentially identical (Table 2). The ventilation rates were sufficiently stable to require no statistical adjustment.

A number of inherent limitations may have caused error in the findings of this study. The modest sample size (230 questionnaires per week) and low baseline levels of indoor contaminants produced an underpowered study. However, the within-person analyses and the representativeness of responders should have prevented bias from low weekly response rates. The use only of subjective self-reported outcome measures made detection of effects more difficult due to potentially increased misclassification. Comparing existing configurations of workers rather than groups of randomly selected individuals, unavoidable in this occupational setting, should not have caused bias, but may have caused slight overestimation of the precision of estimates. If any filtration effects on occupants had residual influence into the next week with a changed filtration condition, findings would be distorted. In fact, exploratory models assuming residual effects estimated generally greater immediate benefits from enhanced filtration on most outcomes.

Back to Top | Article Outline
Possible Mechanisms for Effects Associated with Enhanced Filtration

Available information on the health effects of small particles, mostly concerning outdoor particles, suggest that higher concentrations of small particles influence acute symptoms, hospital admissions, and mortality rates. 32 These exposures, however, probably occur mostly indoors, where people spend 90% of their time, as a high proportion of small particles produced outdoors penetrate indoors. Efficient filtration would reduce exposures to small particles from either indoor or outdoor sources, including aerosols from outdoor combustion or photochemical processes and small fragments of pollens and other bioaerosols. This study did not assess impacts on chronic health effects such as reduced lung function or cardiovascular disease, which have been associated with higher concentrations of particles in outdoor air. 33

The limited available evidence on health effects of airborne particles in indoor work environments, including observational studies 34,35 and experimental studies that removed airborne particles from indoor air, 2,21,36–38 has been mixed. Experimental exposures to office dust have found effects on skin and mucus membranes, headache, concentration difficulty, and confusion. 39,40 Particulate contaminants on indoor surfaces, which may be involved in indoor exposures, have been associated with increased occupant symptoms in previous observational studies, 15,41,42 although findings from experimental studies that reduced surface contaminants have been mixed. 29,43–45 Residential studies have extensively documented adverse health effects of airborne particles and benefits from removal (mostly among allergic or asthmatic individuals) 46; however, exposures to dust mites, pet dander, and fungi may be substantially larger in homes.

Microbiologic measurement results here provided no evidence for important exposures to fungal spores or spore fragments from indoor sources (as assessed by glucans and ergosterol) and did not suggest that filtration reduced the already low endotoxin exposures, which may be associated primarily with larger particles. 47 Furthermore, high efficiency filtration, relative to conventional filtration, would have only modestly reduced exposures (by less than 16%) to large particles such as fungal spores, whole bacteria, pollen grains, and material from dust mites.

Back to Top | Article Outline
Possible Mechanisms for Effects Associated with Temperature and Humidity

For each 1°C decrease within the 22.1–25.6°C range observed, adverse outcomes decreased between 4% and 25% of their mean values. These findings suggest substantial occupant benefits from temperatures at the cooler end of the accepted summer thermal comfort range in air-conditioned buildings. Previously reported studies have found similar relationships of temperature with symptoms, 2,4,13,14 environmental dissatisfaction, 9,48 or both. 49–51 Others, often with less coincident measurements of environment and outcomes, have not seen these relationships. 52 At lower temperatures, the substantial reductions found here in discomfort from excess warmth, stuffiness, humidity, dryness, and dustiness were accompanied by much smaller related increases in discomfort from cold and draft. (One previous study found that average occupant comfort improved continually as temperature fell to 22°C, and only below 22°C did the proportion feeling too cool begin to rise. 48)

Various mechanisms may explain such broad effects of temperature: a reduction of air temperature reducing VOC-related symptoms (Mølhave et al.49); a temperature- and humidity-related perceptual “illusion that cooler and drier air is somehow freer of contaminants” (Berglund and Cain 9); or the production by higher temperature of a sensation of dryness and stuffiness through reduced cooling of mucous membranes (Fang et al.10). The latter has some empirical support. 53

Findings here that changing humidity was not associated with perception of dryness or moisture, although counter-intuitive, have been reported by numerous other researchers (eg, Sundell 18). While many previous experimental studies have found increasing relative humidity to be associated with decreasing acceptability of air, 9,10,53,54 such data cannot be directly compared with findings in this study, which did not assess acceptability of air. By Fang’s hypothesis, 10 increased humidity ratio should increase perceived dryness and stuffiness by decreasing evaporative cooling of mucus membranes. However, increased humidity ratio here was associated with no change in perceived dryness and a small decrease in stuffiness.

The small decreases in symptoms found here with increased humidity ratio were most convincing for throat, chest, and fatigue symptoms. Previous experimental studies have also found decreased symptoms with moderate increases in relative humidity. 2,55,56 Previous cross-sectional studies finding no association between humidity and symptoms (reviewed elsewhere 1) tend to have substantial design limitations, such as a lack of correspondence between humidity measurements and periods of symptom recall. Associations of higher humidities with decreased symptoms would not in themselves justify use of active humidification in indoor environments, because of the decreased acceptability of air associated with increased humidity, 9,10,53,54 and more importantly, the documented risk of respiratory disease and symptoms associated with humidification systems. 57,58

Back to Top | Article Outline
Future Implications

This study demonstrates that air filtration can be used to assess the effects of small particles on occupants in an office building by temporarily decreasing concentrations of these particles 20-fold. This study further demonstrates that controlling in analyses for the strong effects of temperature on reported acute outcomes is critically important in assessing accurately the effects of non-temperature changes. Cross-sectional or experimental studies without such control may erroneously attribute effects of temperature to other factors. In this study, mean temperatures during the four intervention weeks were identical for conditions of enhanced and of regular filtration (23.5°C). Chance differences of even 0.5°C, however, would have produced an almost 10% difference in eye symptoms which, unless corrected by adjustment, would have either hidden or tripled the estimated 4% reduction associated with enhanced filtration.

Findings here are consistent with slight benefits – improved productivity-related mental states and reduced environmental dissatisfaction – from decreased concentrations of small airborne particles in a building without evident contamination. Potential benefits even of the small size found in this study justify continued research, due to the potentially large aggregate benefits for millions of indoor workers. It is uncertain how the performance-related mental states assessed in this study relate to actual performance, but the potential economic gain in performance among occupants may exceed the cost of enhanced filtration more than 8-fold. 59 Similarly, the overall benefits of relatively cooler indoor temperatures for symptoms, thermal comfort, and performance-related mental states, may be large; net benefits found for higher moderate humidities are more uncertain. Clarification of all these relationships will require studies with larger sample size, better-controlled temperature, and possibly higher levels of particles and lower ventilation rates.

Back to Top | Article Outline

Acknowledgments

We thank building occupants and management for their generous cooperation; Mary Prince, Charles Mueller, Caroline Portman, and Ghania LaBrie for assistance with data collection; James M. Thomas, Jr. and Carole Dabrowski for assistance with environmental measurements; Sue Nowlin and Karl Sieber for set-up of hardware and software for the questionnaire; Kathleen Watkins for data entry and assistance with data editing; and Ted Gartner for assistance with graphics.

Back to Top | Article Outline

References

1. Mendell MJ. Non-specific symptoms in office workers: a review and summary of the epidemiologic literature. Indoor Air 1993; 3: 227–236.

2. Wyon DP. Sick buildings and the experimental approach. Environ Technol 1992; 13: 313–322.

3. Franck C, Bach E, Skov P. Prevalence of objective eye manifestations in people working in office buildings with different prevalences of the sick building syndrome compared with the general population. Int Arch Occup Environ Health 1993; 65: 65–69.

4. Wålinder R, Norbäck D, Wieslander G, Smedje G, Erwall C, Venge P. Nasal patency and biomarkers in nasal lavage – the significance of air exchange rate and type of ventilation in schools. Int Arch Occup Environ Health 1998; 71: 479–486.

5. Seppänen O, Fisk WJ, Mendell MJ. Association of ventilation rates and CO2 concentrations with health and other human responses in commercial and institutional buildings. Indoor Air 1999; 9: 226–252.

6. Teeuw KB, Vandenbroucke-Grauls CMJE, Verhoef J. Airborne gram-negative bacteria and endotoxin in sick building syndrome. Arch Intern Med 1994; 154: 2339–2345.

7. Leinster P, Raw G, Thomson N, Leaman A, Whitehead C. A modular longitudinal approach to the investigation of Sick Building Syndrome. Indoor Air 90: Proceedings of the Fifth International Conference on Indoor Air Quality and Climate, 1990; Toronto 1:287–292.

8. Wargocki P, Wyon DP, Baik YK, Clausen G, Fanger PO. Perceived air quality, sick building syndrome (SBS) symptoms and productivity in an office with two different pollution loads. Indoor Air 1999; 9: 165–179.

9. Berglund LG, Cain WS. Perceived air quality and the thermal environment. IAQ ‘89: The human equation – health and comfort. American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc. (ASHRAE) Conference, April 17–20, 1989: San Diego.

10. Fang L, Clausen G, Fanger PO. Impact of temperature and humidity on the perception of indoor air quality. Indoor Air 1998; 8: 80–90.

11. Fang L, Clausen G, Fanger PO. Impact of temperature and humidity on perception of indoor air quality during immediate and longer whole-body exposures. Indoor Air 1998; 8: 276–284.

12. Jaakkola JJK, Heinonen OP, Seppänen O. Mechanical ventilation in office buildings and the sick building syndrome – an experimental and epidemiological study. Indoor Air 1991; 2: 111–121.

13. Menzies R, Tamblyn R, Farant JP, Hanley J, Nunes F, Tamblyn R. The effect of varying levels of outdoor-air supply on the symptoms of sick building syndrome. New Engl J Med 1993; 328: 821–827.

14. Skov P, Valbjørn O, Pedersen BV, the Danish Indoor Climate Study Group. Influence of indoor climate on the sick building syndrome in an office environment. Scand J Work Environ Health 1990; 16: 363–371.

15. Gyntelberg F, Suadicani P, Nielsen JW, et al. Dust and the sick building syndrome. Indoor Air 1994; 4: 223–238.

16. Dales RE, Burnett R, Zwanenburg H. Adverse health effects among adults exposed to home dampness and molds. Am Rev Respir Dis 1991; 143: 505–509.

17. Brunekreef B. Damp housing and adult respiratory symptoms. Allergy 1992; 47: 498–502.

18. Sundell J, Lindvall T. Indoor air humidity and sensation of dryness as risk indicators of SBS. Indoor Air 1993; 3: 382–390.

19. Fisk WJ, Faulkner D, Sullivan D, et al. The healthy building intervention study: objectives, methods, and results of selected environmental measurements. Berkeley, CA: Lawrence Berkeley National Laboratory (LBNL-41546); 1998.

20. American Society for Heating, Refrigerating, and Air-Conditioning Engineers. 1992 ASHRAE Handbook: HVAC systems and equipment. Atlanta, ASHRAE, Inc., 1992.

21. Fisk WJ, Faulkner D, Sullivan S, Mendell MJ. Particle concentrations and sizes with normal and high efficiency air filtration in a sealed air-conditioned office building. Aerosol Sci Technol 2000; 32: 527–544.

22. Baker EL, Letz RE, Fidler AT, Shalat S, Plantamura D, Lyndon M. A computer-based neurobehavioral evaluation system for occupational and environmental epidemiology: methodology and validation studies. Neurobehav Toxicol Teratol 1985; 7: 369–377.

23. Dong MX, Petersen MR, Mendell MJ. Using pilot data to estimate sample size and compare question forms for a crossover study. J Occup Health 1998; 40: 307–312.

24. Hines CJ, Milton DK, Larsson L, Petersen MR, Fisk WJ, Mendell MJ. Characterization and variability of endotoxin and 3-hydroxy fatty acids in an office building during a particle intervention study. Indoor Air 2000; 10: 2–12.

25. Fisk WJ, Mendell MJ, Daisey JM, et al. Phase 1 of the California Healthy Building Study. a summary. Indoor Air 1993; 3: 246–254.

26. Faulkner D, Fisk WJ, Sullivan DP, Thomas JM Jr. Characterizing building ventilation with the pollutant concentration index: results from field studies. Proceedings of IAQ and Energy 1998 (A. Persily, ed.), Oct 24–27, New Orleans;27–35.

27. SAS Institute. Statistical Analysis System (SAS) version 6.12. Cary, NC, SAS Institute, 1996.

28. American National Standards Institute/American Society for Heating, Refrigerating, and Air Conditioning Engineers. Standard 55–1992: Thermal Environmental Conditions for Human Occupancy. Atlanta; ASHRAE, 1992.

29. Raw GJ, Roys MS, Whitehead C. Sick building syndrome: cleanliness is next to healthiness. Indoor Air 1993; 3: 237–245.

30. Tamblyn RM, Menzies R, Tamblyn RT, Farant JP, Hanley J. The feasibility of using a double blind experimental cross-over design to study interventions for sick building syndrome. J Clin Epidemiol 1992; 45: 603–612.

31. Seppänen O, Fisk WJ, Mendell MJ. Association of ventilation rates and CO2 concentrations with health and other human responses in commercial and institutional buildings. Indoor Air 1999; 9: 226–252.

32. Pope AP. Invited commentary: particulate matter-mortality exposure-response relations and threshold. Am J Epidemiol 2000; 152: 407–412.

33. Dockery DW, Pope CA III. Acute respiratory effects of particulate air pollution. Ann Rev Public Health 1994; 15: 107–132.

34. Hodgson MJ, Frohliger J, Permar E, et al. Symptoms and microenvironmental measures in nonproblem buildings. J Occup Med 1991; 33: 527–533.

35. Norbäck D, Torgen M, Edling C. Volatile organic compounds, respirable dust, and personal factors related to prevalence and incidence of sick building syndrome in primary schools. BJM 1990; 47: 733–741.

36. Hedge A, Martin MG, McCarthy JF. Breathing zone filtration effects on IAQ and SBS complaints. Proceedings of the Healthy Buildings ‘91 Conference, ASHRAE, Washington, September 1991:4–8.

37. Rosen KG, Richardson G. Would removing indoor air particulates in children’s environments reduce rate of absenteeism–a hypothesis. Sci Total Environ 1999; 234: 87–93.

38. Wyon DP, Tham KW, Croxford B, Young A, Oreszczyn T. The effects of health and self-estimated productivity of 2 experimental interventions which reduced airborne dust levels in office premises. Proceedings of the Healthy Buildings 2000 Conference, Helsinki, Finland, August 2000;1:641–646.

39. Pan Z, Mølhave L, Kjærgaard SK. Effects on eyes and nose in humans after experimental exposure to airborne office dust. Indoor Air 2000; 10: 237–245.

40. Mølhave L, Kjærgaard SK, Attermann. Sensory and other neurogenic effects of exposures to airborne office dusts. Atmos Environ 2000; 34: 4755–4766.

41. Skov P, Valbjørn O, Danish Indoor Climate Study Group. The “sick” building syndrome in the office environment: the Danish Town Hall Study. Environ Intl 1987; 13: 339–349.

42. Hedge A, Erickson WA, Rubin G. Effects of man-made mineral fibers in settled dust on sick building syndrome in air-conditioned offices. Proceedings of Indoor Air 93: The 6th International Conference on Indoor Air Quality and Climate. 1993; Helsinki, Finland, July 4–8;1:291–96.

43. Skyberg K, Skulberg KR, Kruse K, Huser PO, Levy F, Djupesland P. Dust reduction relieves nasal congestion – a controlled intervention study on the effect of office cleaning using acoustic rhinometry. Proceedings of Indoor Air ’99: The 8th International Conference on Indoor Air Quality and Climate. Edinburgh, Scotland. August 8–13, 1999;1:153–54.

44. Kemp PC, Dingle P, Neumeister HG. Particulate matter intervention study: a causal factor of building-related symptoms in an older building. Indoor Air 1998; 8: 153–171.

45. Kildesø; J, Tornvig L, Skov P, Schneider T. An intervention study of the effect of improved cleaning methods on the concentration and composition of dust. Indoor Air 1998; 8: 12–22.

46. Institute of Medicine. Committee on the Assessment of Asthma and Indoor Air. “Impact of ventilation and air cleaning on asthma,” in:Clearing the Air: Asthma and Indoor Air Exposures. National Academy Press: Washington, DC, 2000;327–93.

47. Smid T, Heederik D, Mensink G, Houba R, Boleij JSM. Exposure to dust, endotoxins, and fungi in the animal feed industry. Am Ind Hyg Assoc J 1992; 53: 362–368.

48. Palonen J, Seppänen O, Jaakkola JJK. The effects of air temperature and relative humidity on thermal comfort in the office environment. Indoor Air 1993; 3: 391–397.

49. Mølhave L, Liu A, Jørgensen AH, Pedersen OF, Kjærgaard SK. Sensory and physiological effects on humans of combined exposures to air temperatures and volatile organic compounds. Indoor Air 1993; 3: 155–169.

50. Reinikainen LM, Jaakkola JJK. The effect of room temperature on symptoms and perceived indoor air quality in office workers – a six week longitudinal study. Proceedings of Indoor Air 93: The 6th International Conference on Indoor Air Quality and Climate. 1993;1:47–52.

51. Jaakkola JJK, Heinonen OP, Seppänen O. Sick building syndrome, sensation of dryness and thermal comfort in relation to room temperature in an office building: need for individual control of temperature. Environ Int 1989; 15: 163–168.

52. Sundell J, Lindvall T. Indoor air humidity and the sensation of dryness as risk indicators of SBS. Indoor Air 1993; 3: 382–390.

53. Toftum J, Jørgensen AS, Fanger PO. Effect of humidity and temperature of inspired air on perceived comfort. Energy Buildings 1998; 28: 15–23.

54. Reinikainen LM, Aunela-Tapola L, Jaakkola JJK. Humidification and perceived indoor air quality in the office environment. Occup Environ Med 1997; 54: 322–327.

55. Kay DLC, Heavner DL, Nelson PR, et al. Effects of relative humidity on nonsmoker response to environmental tobacco smoke. Proceedings of Indoor Air 1990: The 5th Intl Conf on Indoor Air Quality and Climate, Toronto, July 29-Aug 3, 1990;1:275–279.

56. Reinikainen LM, Jaakkola JJK, Seppänen O. The effect of air humidification on symptoms and perceptions of indoor air quality in office workers: a six-period cross-over trial. Arch Environ Health 1993; 47: 8–15.

57. Forsgren A, Persson K, Ursing J, Walder M, Borg I. Immunological aspects of humidifier fever. Eur J Clin Microbiol 1984; 3: 411–418.

58. Zweers T, Preller L, Brunekreef B, Boleij JSM. Health and indoor climate complaints of 7043 office workers in 61 buildings in the Netherlands. Indoor Air 1992; 2: 127–136.

59. Fisk WJ. Health and productivity gains from better indoor environments and their relationship with building energy efficiency. Annu Rev Energy Environ 2000; 25: 537–566.

Cited By:

This article has been cited 35 time(s).

International Journal of Hygiene and Environmental Health
Indoor air pollutants in office environments: Assessment of comfort, health, and performance
Wolkoff, P
International Journal of Hygiene and Environmental Health, 216(4): 371-394.
10.1016/j.ijheh.2012.08.001
CrossRef
Presse Medicale
The sick building syndrome (SBS)
Ezratty, V
Presse Medicale, 32(): 1572-1579.

International Journal of Epidemiology
Workplace air-conditioning and health services attendance among French middle-aged women: a prospective cohort study
Preziosi, P; Czernichow, S; Gehanno, P; Hercberg, S
International Journal of Epidemiology, 33(5): 1120-1123.
10.1093/ije/dyh136
CrossRef
ASHRAE Transactions 2005, Vol 111, Pt 2
Control of temperature for health and productivity in offices
Seppanen, O; Fisk, WJ; Faulkner, D
ASHRAE Transactions 2005, Vol 111, Pt 2, 111(): 680-686.

Hvac&R Research
Some quantitative relations between indoor environmental quality and work performance or health
Seppanen, OA; Fisk, W
Hvac&R Research, 12(4): 957-973.

Occupational and Environmental Medicine
Is health in office buildings related only to psychosocial factors?
Mendell, MJ; Fisk, WJ
Occupational and Environmental Medicine, 64(1): 69.

Indoor Air 2005: Proceedings of the 10Th International Conference on Indoor Air Quality and Climate, Vols 1-5
An integrated approach to eye irritation in the office - Importance of the relative humidity?
Wolkoff, P
Indoor Air 2005: Proceedings of the 10Th International Conference on Indoor Air Quality and Climate, Vols 1-5, (): 3777-3781.

Indoor Air
Risk factors in heating, ventilating, and air-conditioning systems for occupant symptoms in US office buildings: the US EPA BASE study
Mendell, MJ; Lei-Gomez, Q; Mirer, AG; Seppanen, O; Brunner, G
Indoor Air, 18(4): 301-316.
10.1111/j.1600-0668.2008.00531.x
CrossRef
Indoor and Built Environment
Numerical investigation of particle diffusion in a clean room
Zhao, B; Wu, J
Indoor and Built Environment, 14(6): 469-479.
10.1177/1420326X060190
CrossRef
Building and Environment
Particle dispersion and deposition in ventilated rooms: Testing and evaluation of different Eulerian and Lagrangian models
Zhao, B; Yang, C; Yan, X; Liu, S
Building and Environment, 43(4): 388-397.
10.1016/j.buildenv.2007.01.005
CrossRef
Indoor and Built Environment
The Applicability of Epidemiological Methods to the Assessment of the Risks to Human Health of Indoor Air Pollution: An Overview
Brown, T; Holmes, P; Harrison, PTC
Indoor and Built Environment, 19(3): 311-326.
10.1177/1420326X09342683
CrossRef
Indoor Air 2005: Proceedings of the 10Th International Conference on Indoor Air Quality and Climate, Vols 1-5
Some quantitative relations between indoor environmental quality and work performance or health
Seppanen, O; Fisk, WJ
Indoor Air 2005: Proceedings of the 10Th International Conference on Indoor Air Quality and Climate, Vols 1-5, (): P40-P53.

Building and Environment
Reducing particle exposures in a tropical office building using electrostatic precipitators
Zuraimi, MS; Tham, KW
Building and Environment, 44(): 2475-2485.
10.1016/j.buildenv.2009.04.011
CrossRef
Indoor Air
Persistent allergic rhinitis and indoor air quality perception - an experimental approach
Graudenz, GS; Latorre, MRDO; Tribess, A; Oliveira, CH; Kalil, J
Indoor Air, 16(4): 313-319.
10.1111/j.1600-0668.2006.00428.x
CrossRef
Building and Environment
Application of artificial neural networks to predict prevalence of building-related symptoms in office buildings
Sofuoglu, SC
Building and Environment, 43(6): 1121-1126.
10.1016/j.buildenv.2007.03.003
CrossRef
Building and Environment
Numerical analysis of particle deposition in ventilation duct
Zhao, B; Chen, JJ
Building and Environment, 41(6): 710-718.
10.1016/j.buildenv.2005.02.030
CrossRef
Indoor Air
The modern office environment desiccates the eyes?
Wolkoff, P; Nojgaard, JK; Franck, C; Skov, P
Indoor Air, 16(4): 258-265.
10.1111/j.1600-0668.2006.00429.x
CrossRef
Environmental Health Perspectives
Hydrophilic fungi and ergosterol associated with respiratory illness in a water-damaged building
Park, JH; Cox-Ganser, JM; Kreiss, K; White, SK; Rao, CY
Environmental Health Perspectives, 116(1): 45-50.
10.1289/ehp.10355
CrossRef
Environment International
"Healthy" eye in office-like environments
Wolkoff, P
Environment International, 34(8): 1204-1214.
10.1016/j.envint.2008.04.005
CrossRef
Indoor Air
Indices for IEQ and building-related symptoms
Mendell, MJ
Indoor Air, 13(4): 364-368.

Indoor Air
Do indoor pollutants and thermal conditions in schools influence student performance? A critical review of the literature
Mendell, MJ; Heath, GA
Indoor Air, 15(1): 27-52.
10.1111/j.1600-0668.2004.00320.x
CrossRef
Building and Environment
Could sperm quality be affected by a building environment? A literature review
Song, GS
Building and Environment, 45(4): 936-943.
10.1016/j.buildenv.2009.09.016
CrossRef
Indoor and Built Environment
Numerical study of particle deposition in two differently ventilated rooms
Zhao, B; Li, XT; Zhang, Z
Indoor and Built Environment, 13(6): 443-451.
10.1177/1420326X04048729
CrossRef
Occupational and Environmental Medicine
Eye complaints in the office environment: precorneal tear film integrity influenced by eye blinking efficiency
Wolkoff, P; Nojgaard, JK; Troiano, P; Piccoli, B
Occupational and Environmental Medicine, 62(1): 4-12.
10.1136/oem.2004.016030
CrossRef
Environment International
The dichotomy of relative humidity on indoor air quality
Wolkoff, P; Kjaergaard, SK
Environment International, 33(6): 850-857.
10.1016/j.envint.2007.04.004
CrossRef
Indoor Air
Symptoms, complaints, ocular and nasal physiological signs in university staff in relation to indoor environment - temperature and gender interactions
Bakke, JV; Norback, D; Wieslander, G; Hollund, BE; Florvaag, E; Haugen, EN; Moen, BE
Indoor Air, 18(2): 131-143.
10.1111/j.1600-0668.2007.00515.x
CrossRef
Periodicum Biologorum
SICK BUILDING SYNDROME Do we live and work in unhealthy environment?
Gomzi, M; Bobic, J
Periodicum Biologorum, 111(1): 79-84.

Indoor Air
Indoor thermal factors and symptoms in office workers: findings from the US EPA BASE study
Mendell, MJ; Mirer, AG
Indoor Air, 19(4): 291-302.
10.1111/j.1600-0668.2009.00592.x
CrossRef
Atmospheric Environment
Comparison of the Eulerian and Lagrangian methods for predicting particle transport in enclosed spaces
Zhang, Z; Chen, Q
Atmospheric Environment, 41(): 5236-5248.
10.1016/j.atmosenv.2006.05.086
CrossRef
Indoor Air 2005: Proceedings of the 10Th International Conference on Indoor Air Quality and Climate, Vols 1-5
Perception patterns of indoor air quality from volunteers with persistent allergic rhinitis
Graudenz, GS; do Rosario, M; Latorre, DO; Tribess, A; Oliveira, CH; Kalil, J
Indoor Air 2005: Proceedings of the 10Th International Conference on Indoor Air Quality and Climate, Vols 1-5, (): 6-10.

Occupational and Environmental Medicine
Sick building syndrome
Burge, PS
Occupational and Environmental Medicine, 61(2): 185-190.
10.1136/oem.2003.008813
CrossRef
Asia-Pacific Journal of Public Health
The discovery of an unusual cause of indoor radiation pollution
Chaiear, N; Saejiw, N; Dithisawatwet, S; Polpila, P; Paratako, K; Chuntum, K
Asia-Pacific Journal of Public Health, 18(2): 46-50.

Drug and Alcohol Dependence
The built environment and alcohol consumption in urban neighborhoods
Bernstein, KT; Galea, S; Ahern, J; Tracy, M; Vlahov, D
Drug and Alcohol Dependence, 91(): 244-252.
10.1016/j.drugalcdep.2007.06.006
CrossRef
Environmental Toxicology
Were volatile organic compounds the inducing factors for subjective symptoms of employees working in newly constructed hospitals?
Takigawa, T; Horike, T; Ohashi, Y; Kataoka, H; Wang, DH; Kira, SH
Environmental Toxicology, 19(4): 280-290.
10.1002/tox.20035
CrossRef
Journal of Environmental Protection and Ecology
Sick-Building Syndrome
Sarafis, P; Sotiriadou, K; Dallas, D; Stavrakakis, P; Chalaris, M
Journal of Environmental Protection and Ecology, 11(2): 515-522.

Back to Top | Article Outline